NFPA 75 – Standard for the Fire Protection of Information Technology Equipment
۲۰۲۰ Edition
Chapter 1 Administration
۱-۱ Scope. This standard covers the requirements for the protection of information technology equipment (ITE) and ITE areas.
۱-۲* Purpose. The purpose of this standard is to set forth the minimum requirements for the protection of ITE equipment and ITE areas from damage by fire or its associated effects — namely, smoke, corrosion, heat, and water.
۱-۳* Application. The application of this standard is based on the risk considerations outlined in Chapter 4.
۱-۳-۱ A documented risk assessment shall be the basis for implementation of this standard.
۱-۳-۲ The mere presence of the ITE shall not constitute the need to invoke the requirements of this standard.
N 1-3-3 If applied, the requirements of this standard shall include the installation of ITE in modular data centers, fabricated containers, and other groupings.